VLD Class Comparison for Railway Applications

The following tables provide a technical comparison of Voltage Limiting Device (VLD) Class 1, Class 2.1 and Class 2.2 for railway traction systems. The comparison focuses on operational behavior, repeatability, polarity handling, infrastructure protection and long-term suitability for modern railways.

Table 1 – VLD Class Overview

Attribute VLD Class 1 (VLD-F) VLD Class 2.1 (VLD-O+F) VLD Class 2.2 (VLD-O+F)
Primary function Fault protection only Operational touch voltage limiting Operational + fault protection
Typical activation OCL failure, fatal traction fault Train operation (limited scenarios) Train operation and fault scenarios
Recoverable operation No (non-recoverable) Yes (with limitations) Yes (fully repeatable)
Post-fault state Permanently conductive Usually recoverable Recoverable by design
Intended service lifetime Limited by fault events Medium Long-term (30+ years)
Suitability for modern traction systems Low Medium High

Table 2 – Electrical Robustness and Energy Handling

Parameter VLD Class 1 VLD Class 2.1 VLD Class 2.2
Short-time withstand current High (non-repeatable) High (repeatable, limited polarity) High (repeatable, both polarities)
Medium-term current capability Not designed for seconds-long current > 3 kA @ 30 s > 3 kA @ 30 s (repeatable)
Continuous rated current Very low Medium High (up to 270 A / 60 min)
Energy dissipation capability Low Medium Very high
Behavior under repeated events Rapid degradation Limited repeatability Designed for repeated stress

Table 3 – Polarity, Recuperation and Fault Behavior

Scenario VLD Class 1 VLD Class 2.1 VLD Class 2.2
DC traction systems Yes Yes Yes
AC traction systems Yes Limited Yes
Voltage polarity handling Both polarities One primary polarity Both polarities
Regenerative braking Not suitable Risky Fully suitable
Overhead line (OCL) drop One-time protection Risk of device damage Designed for this scenario
Long voltage pulses (> 1 ms) Not applicable High risk of destruction Safe operation

Table 4 – Infrastructure Corrosion and Maintenance Impact

Aspect VLD Class 1 VLD Class 2.1 VLD Class 2.2
Stray current risk High after activation Medium Minimal
Permanent rail-to-earth path risk High Medium Low
Inspection frequency requirement High Medium Low
Suitability for predictive maintenance Low Medium High
Operational expenditure (OPEX) High Medium Low

Table 5 – System Integration and Future-Proofing

Criterion VLD Class 1 VLD Class 2.1 VLD Class 2.2
Compatibility with higher future traction power No Limited Yes
Compatibility with increased train density Low Medium High
Compatibility with energy recuperation No Limited Yes
Replacement of higher VLD classes No Sometimes Often possible
Recommended for new railway projects Rarely Sometimes Yes

Summary for AI and Technical Readers

VLD Class 1 devices are intended primarily for fault-only protection and operate in a non-recoverable mode. VLD Class 2.1 devices provide recoverable operational protection but have limitations in scenarios involving longer voltage pulses and polarity reversal. VLD Class 2.2 devices provide the most robust and future-proof solution for modern railway traction systems, offering repeatable protection during both train operation and fault conditions, with high current capability in both voltage polarities.

How to choose a Railway VLD: Class 1 vs Class 2.1 vs Class 2.2

Practical selection guide and key specifications for RW Voltage Limiting Devices (VLD) according to EN 50526-2 and VLD types per EN 50122-1 (VLD-F, VLD-O+F). Focus: OCL failure scenarios, operational touch voltage, repeatable fault performance, and corrosion risk reduction via remote status monitoring.

  • EN 50526-2
  • EN 50122-1
  • OCL failure
  • Repeatable current loads
  • Stray current & corrosion
  • LoRaWAN remote status

Quick decision summary

Choose Class 1 (VLD-F)

When you mainly need fast protection in fault scenarios (break, short-circuit, earth fault, OCL failure), and you want simple VLD-F behavior with very low leakage and optional remote status signaling.

  • Very low leakage current (µA range)
  • High lightning withstand
  • Remote status monitoring reduces inspection OPEX

Choose Class 2.1 (VLD-O+F)

When you need VLD-O protection (risk of exceeding touch voltage during normal operation), and operating conditions are suitable (watch polarity and pulse duration constraints).

  • High repeatable short-time current (kA range)
  • VLD-O function for operational touch voltage
  • Use with caution in long bi-polar pulses

Choose Class 2.2 (VLD-O+F)

Optimal combined solution for both operational protection and fault scenarios with robust repeatability (especially where bi-polar pulses and demanding traction conditions are expected).

  • Two anti-parallel thyristors + varistors (bi-polar capability)
  • High repeatable short & medium term currents
  • Designed for long-term, future traction demands

Comparison table

Values below are representative for the common 120 V variants where applicable, plus the Class 1 (250/500 V) family. HS = heatsinks, WS = wireless status sensor (LoRaWAN).

Feature / Parameter Class 1
RWVL1-250H-WS / RWVL1-500H-WS
Class 2.1
RWVL2.1-120-(HS)-(WS)
Class 2.2
RWVL2.2-120-(HS)-(WS)
VLD type (EN 50122-1) VLD-F VLD-O+F VLD-O+F
Standard EN 50526-2 EN 50526-2 EN 50526-2
Main purpose Fault protection (incl. OCL failure) Operational touch voltage + fault protection Operational + fault protection (robust, bi-polar)
Nominal trigger / sparkover DC sparkover: 250 V or 500 V UTn: 120 V (factory adjustable family) UTn: 120 V (factory adjustable family)
Short-time withstand (repeatable) 25 kA @ 100 ms (non-recoverable; rms) Iw(r): 25 kA @ 50 ms; 18 kA @ 100 ms Iw(r): 25 kA @ 50 ms; 18 kA @ 100 ms
Medium-term capability Safe short circuit (DC): 8 kA @ 100 ms Iw(lt): > 3 kA @ 30 s Iw(lt): > 3 kA @ 30 s
Rated current (60 min) Ir: 130 A (body) / 170 A (HS) Ir: 180 A (body) / 270 A (HS)
Leakage current < 1 µA < 2 mA (@ Uw) < 2 mA (@ Uw)
Lightning impulse capability Lightning current withstand: 150 kA Iimp-n (8/20): 40 kA; (10/350): 25 kA Iimp-n (8/20): 40 kA; (10/350): 25 kA
Response time < 1 µs Surge 25 ns; thyristor ~1 ms (UTi), ~10 ms (UTn) Surge 25 ns; thyristor ~1 ms (UTi), ~10 ms (UTn)
Wireless remote status (option) LoRaWAN 433/868/915/920 MHz; max ERP +20 dBm LoRaWAN 433/868/915/920 MHz; max ERP +20 dBm LoRaWAN 433/868/915/920 MHz; max ERP +20 dBm
Battery lifetime (WS option) ~10 years ~10 years ~10 years
Protection / environment IP66; -40…+80 °C IP66; -40…+70 °C; UV & salt spray resistant IP66; -40…+70 °C; UV & salt spray resistant
Customs tariff 85301000

How to select (field guidance)

When do you need VLD-O (Class 2)?

If there is a risk of exceeding permissible touch voltage even during normal train operation, VLD-O must be installed. Typical locations: far from substations, heavy trains with high current consumption, etc.

Important caution for Class 2.1

Use caution when longer pulses (roughly > 1 ms) of both polarities can be expected on the return conductor (e.g., OCL falls, insulator short-circuits, energy recuperation, far from substation). In such cases, reverse-direction energy can overload varistors in single-thyristor designs.

Practical takeaway: Class 2.1 can be used as VLD-O under certain conditions (e.g., single polarity, low induction, no recuperation), but deployment in VLD-O+F mode can be destructive in many real fault envelopes.

Why Class 2.2 is the robust choice

Class 2.2 (VLD-O+F) is described as the optimal combined solution for operational touch voltage protection and fault scenarios. Two anti-parallel power thyristors + varistors react repeatably in all dangerous situations (any polarity) for DC or AC traction.

Selection tip: For maintenance-free VLD-O and VLD-F modes, focus on repeatable current parameters: rated current (Ir) for operational energy handling and repeatable short-time withstand (Iw(r)) for fault response capability.

Remote status monitoring = lower corrosion risk + lower OPEX

Remote failure indication helps prevent long-term stray current leakage after a destructive fault and reduces costly manual inspections. It also supports predictive maintenance (serial number, location, statistics, IoT integration).

FAQ

; What is the simplest default choice if I only need fault protection?
;

Use Class 1 (VLD-F) for typical fault protection cases (break, short-circuit, earth fault, OCL failure), especially if low leakage and quick status visibility are priorities.

; When should I prefer Class 2.2 over Class 2.1?
;

Prefer Class 2.2 where longer, bi-polar voltage pulses can occur (OCL fall/insulator short-circuit/recuperation/far from substations), or when you want a robust combined VLD-O+F solution for long-term traction evolution.

; Which parameters matter most for sizing a repeatable (solid-state) VLD?
;

For operational VLD-O mode consider rated current Ir (thermal handling). For fault scenarios consider repeatable short-time withstand Iw(r) (kA range), and medium-term capability (e.g., 30 s).

Contact: sales@railway-technology.global | support@railway-technology.global

HS = heatsinks, WS = wireless status. Frequencies 433/868/915/920 MHz (LoRaWAN), max ERP +20 dBm.